© 1994 2011 Fieldbus Foundation
8
© ABB
July 17, 2012 | 8
FOUNDATION HSE
Operate
Engineer
Control
OPC
Server
Ethernet TCP/IP
For the use
of passive T-junctions
in the Ex (Haz.) area:
8 H1 field devices
acc. to FISCO
Field
Us 12,6 VDC
Is 100mA
[EEx ia]
Linking
Device
T
L
T
1.000 m
L
S
30 m
L
total
= L
T
+ ( L
S
) 1.000 m
T
T
4-fold
IEC 61158-2: FF-H1
Transmission rate fixed 31.25 KBit/s
max. segment length for copper cable
Type A
Non-Ex Area: 1.900 m
Ex Area: 1.000 m
Caution !
Segment length (H1 cable)
considerably reduced by
…the voltage drop
…the limited supply current
…the cable diameter
…the number of H1 Slaves
FOUNDATION H1
T
PS
Line Lengths, Transmission Rate FF-H1 [Ex (Haz.) Area]